Non-Contact Phase Rotation Indicator
The indicator is suitable for square wave signals can be made from an exclusive-OR (XOR) logic gate. When the two signals being compared are completely in-phase, the XOR gates output will have a constant level of zero,traditional phase sequence measurement methods must poke the three-phase wire terminal, and connect the three bare alligator clips or test pins of phase sequence meters to the three bare firing lines, while PHDE-3002 uses clamp non-contact measurement, without taking off the wire and no need to contact high-voltage bare fire-wire, the test can be made by directly clamping the three-phase insulating sheath by three super-sensitive high-insulated clamps. Conducting measurement on sheathed cable significantly improves the safety of field testing, effectively protect the operator’s personal safety and increase productivity!
Function:
-Phase detection (normal phase, reverse phase and phase deficiency),
-Live wire examination, Simple Power detection,
-Breakpoint location and Line maintenance.
Technical Specifications
Functions
|
Phase detection (normal phase, reverse phase and phase deficiency), Live wire examination, Simple Power detection, Breakpoint location and Line maintenance.
|
Power Supply
|
DC3V AA Mn batteries (R6P) ×2 PCS, Continuously working for 200 hours
|
Live Voltage Range
|
AC0~600V, 40~70Hz (Sine Wave Continuous Input)
|
Clamp Wire Size
|
Diameter ø10-ø40mm
|
LED Display
|
(Positive phase)Four lights of phase detection rotate in Clockwise direction, with intermittent short beeps
(Reverse phase)Four lights of phase detection rotate in counterclockwise direction, continuous beep
(Live power) R-S and S-T lights on within voltage setting range
(Phase deficiency)R-S, S-T lights do not flash
(Open circuit)R-S, S-T lights do not flash
|
Boot Indication
|
Boot indication light turns on after booting
|
Auto Power off
|
After 3 minutes, the meter automatically cut off power supply.
|
Meter Dimension
|
Width, height, thickness 70mm×75mm×30mm
|
Clamp Lead Length
|
0.5m
|
Meter Weight
|
180g (with battery)
|
Working Temperature and Humidity
|
-10℃~55℃; below 80%rh
|
Storage Temperature and Humidity
|
-20℃~60℃; below 90%rh
|
Maximum Measured Voltage
|
AC600V
|
Dielectric Strength
|
5.4kVrms
|
Maximum rated Power
|
100mVA
|
Safety Provisions
|
EN61010-1: 2001, EN61010-031: 2002, Pollution level 2, CAT Ⅲ(600V), Transient over-voltage 6000V
|
Accessories
|
Meter: 1 Piece; Carrying case; 1 Piece.
|